CVE-2017-14471

EUVD-2017-5974
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTPrimary
10 CRITICAL
NETWORK
LOW
NONE
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
talosCNA
10 CRITICAL
NETWORK
LOW
NONE
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
Base Score
CVSS 3.x
EPSS Score
Percentile: 97%
Affected Products (NVD)
VendorProductVersion
rockwellautomationmicrologix_1400_b_firmware
𝑥
≤ 21.2
𝑥
= Vulnerable software versions