A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition  or leak the memory past the allocated structure.
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTPrimary
6.5 MEDIUM
NETWORK
HIGH
NONE
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H
siemensCNA
6.5 MEDIUM
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C
Base Score
CVSS 3.x
EPSS Score
Percentile: 69%
Affected Products (NVD)
VendorProductVersion
siemenssimotics_connect_400_firmware
𝑥
< 0.5.0.0
siemensnucleus_net
*
siemensnucleus_readystart_v3
𝑥
< 2017.02.3
siemensnucleus_readystart_v4
𝑥
< 4.1.0
siemensnucleus_source_code
-
𝑥
= Vulnerable software versions