CVE-2021-32986

After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTNIST
9.8 CRITICAL
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
icscertCNA
9.8 CRITICAL
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVEADP
---
---
CISA-ADPADP
---
---
Base Score
CVSS 3.x
EPSS Score
Percentile: 41%
VendorProductVersion
automationdirectc0-10dd1e-d_firmware
𝑥
< 3.00
automationdirectc0-10dd2e-d_firmware
𝑥
< 3.00
automationdirectc0-10dre-d_firmware
𝑥
< 3.00
automationdirectc0-10are-d_firmware
𝑥
< 3.00
automationdirectc0-11dd1e-d_firmware
𝑥
< 3.00
automationdirectc0-11dd2e-d_firmware
𝑥
< 3.00
automationdirectc0-11dre-d_firmware
𝑥
< 3.00
automationdirectc0-11are-d_firmware
𝑥
< 3.00
automationdirectc0-12dd1e-d_firmware
𝑥
< 3.00
automationdirectc0-12dd2e-d_firmware
𝑥
< 3.00
automationdirectc0-12dre-d_firmware
𝑥
< 3.00
automationdirectc0-12are-d_firmware
𝑥
< 3.00
automationdirectc0-12dd1e-1-d_firmware
𝑥
< 3.00
automationdirectc0-12dd2e-1-d_firmware
𝑥
< 3.00
automationdirectc0-12dre-1-d_firmware
𝑥
< 3.00
automationdirectc0-12are-1-d_firmware
𝑥
< 3.00
automationdirectc0-12dd1e-2-d_firmware
𝑥
< 3.00
automationdirectc0-12dd2e-2-d_firmware
𝑥
< 3.00
automationdirectc0-12dre-2-d_firmware
𝑥
< 3.00
automationdirectc0-12are-2-d_firmware
𝑥
< 3.00
𝑥
= Vulnerable software versions