CVE-2022-2502

EUVD-2022-34760
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTPrimary
7.5 HIGH
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Hitachi EnergyCNA
7.5 HIGH
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Base Score
CVSS 3.x
EPSS Score
Percentile: 17%
Affected Products (NVD)
VendorProductVersion
hitachienergyrtu500_firmware
13.3.1
hitachienergyrtu500_firmware
13.3.2
hitachienergyrtu500_firmware
13.3.3
hitachienergyrtu500_firmware
13.4.1
𝑥
= Vulnerable software versions