CVE-2022-4608
EUVD-2022-5194026.07.2023, 06:15
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.Enginsight
Affected Products (NVD)
| Vendor | Product | Version |
|---|---|---|
| hitachienergy | rtu500_firmware | 13.3.1 |
| hitachienergy | rtu500_firmware | 13.3.2 |
| hitachienergy | rtu500_firmware | 13.3.3 |
| hitachienergy | rtu500_firmware | 13.4.1 |
𝑥
= Vulnerable software versions
Common Weakness Enumeration