CVE-2022-46670

EUVD-2022-49466
Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution.  The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website. 

Cross-site Scripting
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTPrimary
7.1 HIGH
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L
RockwellCNA
7.1 HIGH
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L
Base Score
CVSS 3.x
EPSS Score
Percentile: 10%
Affected Products (NVD)
VendorProductVersion
rockwellautomationmicrologix_1400_firmware
-
rockwellautomationmicrologix_1100_firmware
-
rockwellautomationmicrologix_1400-b_firmware
𝑥
≤ 21.007
rockwellautomationmicrologix_1400-c_firmware
𝑥
≤ 21.007
rockwellautomationmicrologix_1400-a_firmware
𝑥
≤ 7.000
𝑥
= Vulnerable software versions