CVE-2025-2523

The Honeywell Experion PKS 

 and OneWireless WDM 

contains an Integer Underflow 

vulnerability 

in the component ControlData Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failureduring subtraction allowing remote code execution.



Honeywell recommends updating to the most recent version of 

Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1.



The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E.  The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Wrap or Wraparound
ProviderTypeBase ScoreAtk. VectorAtk. ComplexityPriv. RequiredVector
NISTNIST
9.4 CRITICAL
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
HoneywellCNA
9.4 CRITICAL
NETWORK
LOW
NONE
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
CISA-ADPADP
---
---